Assessing The Impact of Natural Ventilation on Thermal Comfort in Public Healthcare Facilities in Adama

dc.contributor.advisorBelay Zeleke (PhD)
dc.contributor.authorMichael, Yeshigeta
dc.date.accessioned2025-12-16T14:11:46Z
dc.date.issued2025-06
dc.description.abstractIn Regions Like Adama, Ethiopia, Where Active Cooling Facilities Are Few, Natural Ventilation Hospital Building Design Is Crucial For Thermal Comfort. The Study Explains How The Indoor Thermal Environment Of Public Health Buildings Is Affected By Design Parameters?�?Window Orientation, Ventilation Strategies, Internal Layout, And Window-To-Floor Ratios. Due To The Vulnerability Of The Occupants Of The Hospital, I.E., Healthcare Staff And Patients, Research Highlights The Contribution Of Passive Design In Maintaining Environmental Quality And Human Well-Being. A Mixed-Methods Approach Was Used, Combining On-Site Environmental Measurement, Architectural Survey, And Occupant Surveys. The Measurements Of Temperature, Relative Humidity, And Air Velocity Were Made At Different Times Of The Day To Capture Diurnal Cycles, And Architectural Features Were Compared With Planned Prototype Designs By GTZ And The Federal Ministry Of Health. Special Studies Were Conducted On Maternity And Inpatient Wards Considering Important Factors Such As Exposure Of Windows, Openness Of Corridors, Ceiling Height, And Potential For Cross-Ventilation. Occupant Surveys Provided Data On Thermal Sensation, Perceived Air Quality, And Window-Use Behavior. Results Indicated A Clear Relationship Between Design And Thermal Comfort: East- Or West-Facing Window Zones Were Warmer, Especially In Midday Sun; Cross-Ventilation Zones Were Significantly Cooler; And Window-To-Floor Area Ratio Less Than 0.2 Zones Were Significantly Less Comfortable. The Study Rated The Buildings According To Their Natural Ventilation Efficiency And Identified Weak And Strong Points In Their Design. In General, The Study Illustrates That Simple Yet Effective Passive Design Principles Such As Maximizing Open Window Openings, Openings' Location With Respect To Prevailing Winds, And Provision For Cross-Ventilation Can Greatly Contribute To Thermal Comfort In Semi-Arid Health Environments. These Findings Offer Useful Lessons For Retrofitting Current Buildings And Creating Tomorrow's Climate-Responsive, Sustainable Health Buildings.en_US
dc.description.sponsorshipASTUen_US
dc.identifier.urihttp://10.240.1.28:4000/handle/123456789/786
dc.language.isoen_USen_US
dc.publisherASTUen_US
dc.subjectNatural ventilation, thermal comfort, healthcare facilities, window-to-floor ratio, cross-ventilation, passive design, public health buildings, climate-sensitive architecture,en_US
dc.subjectNatural Ventilation, Thermal Comfort, Healthcare Facilities, Window-To-Floor Ratio, Cross-Ventilation, Passive Design, Public Health Buildings, Climate-Sensitive Architecture,En_US
dc.titleAssessing The Impact of Natural Ventilation on Thermal Comfort in Public Healthcare Facilities in Adamaen_US
dc.titleAssessing The Impact Of Natural Ventilation On Thermal Comfort In Public Healthcare Facilities In AdamaEn_US
dc.typeThesisen_US

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Michael Yeshigeta.pdf
Size:
3.94 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
1.71 KB
Format:
Plain Text
Description:

Collections